PEL-2000 Programming Manual
46
MIN
Sets to the minimum level
MAX
Sets the voltage limit to
the maximum level
Example
:CONF:PROT:VOLT:LEV MAX
Sets the voltage limit to
81.6V (PEL2020)
Query Syntax
: CONFigure:PROTection:VOLTage:LEVel? [MIN|MAX]
Return Parameter
<NRf> 1 unit = 1 volt
Voltage protection level
1.00
1.00 volts.
MAX/MIN
Returns the allowable
maximum and minimum.
Query Example
:CONF:PROT:VOLT:LEV?
81.6000
Voltage protection level
is at 81.6V.
:CONFigure:PROTection:POWer:STATe
Channel Specific
Command
Description
Sets the power protection for the current/specific
channel on or off. The power protection can also be
cleared.
Syntax
:CONFigure:PROTection:POWer:STATe
{OFF|0|ON|1|CLEAR|2}
Parameter
CLEAR/2
Cleared
OFF/0
Off
ON/1
On
Example
:CONF:PROT:POW:STAT 1
Turns on power protection.
Query Syntax
: CONFigure:PROTection:POWer:STATe?
Return Parameter
<NR1>
Power Protection
0
Off
1
On
2
Clear
Query Example
:CONF:PROT:POW:STAT?
1
Power protection is
currently on.
Vedere la pagina 45